Specifications:
- No. of input channel: 4 channels
- Type of Input sensor: PT100 JIS C1604-1997; JPT100 JIS C1604-1981 , KS C1603-1991
- Input Range of Temperature: PT100 – 200 ~ 600℃ ; JPT100 -200 ~ 600℃
- Digital output: PT100 -2000 ~ 6000; JPT100 -2000 ~ 6000
- Scaling display: 0 ~ 4000
- Accuracy; Normal temp.(25℃)
- Within ±0.3%: Full temp.(0~55℃) Within ±0.5%
- Conversion speed: 40ms / channel
- Insulation – Channel to Channel: Non-insulation
- Terminal to PLC Power: Insulation (Photo-Coupler)
- Terminal block: 15-point terminal block
- I/O points occupied: Fixed type: 64 points
- Wiring method: 3-wire
- Max. number of equipment : 7 (when using XBM (C) – DxxxS type), 10 (when using XB(E)C – DxxxH type)
- Function – Filtering Digital filter (160 ~ 64000 ms)
- Alarm: Disconnection detection
- Current consumption: inner DC5V 100㎃; external DC 24V 100㎃