EL9410 Beckhoff Power Supply Terminal
Description:
The Beckhoff Power Supply Terminal EL9410 is used to refresh the E-bus. Data is exchanged between Coupler and Ethernet terminals via e-bus. Draws a certain amount of current from each terminal e-bus (see “Current cost e-bus” in technical data).
This current is fed to the e-bus by the power supply unit of the relevant coupler. The EL9410 can be used to provide an additional 2 A on the e-bus in a configuration with a large number of terminals. The EL9410 has a diagnostic function as shown by the LED and in the process diagram.
Specification:
Technology | Power supply terminal |
Short-circuit proof | yes |
Input voltage | 24 VDC (-15 %/+20 %) |
Input current | typ. 70 mA + (E-bus/4) |
Output voltage | 5 V for E-bus supply |
Output current | 2 A |
Current consumption E-bus | – |
Electrical isolation | 500 V (E-bus/field potential) |
Power contacts | max. 24 V DC/max. 10 A |
Diagnostics in the process image | yes |
Special features | standard EL supply |
Weight | approx. 65 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Pluggable wiring | for all ESxxxx terminals |
Approvals/markings | CE, UL, ATEX |
Reviews
There are no reviews yet.